Example Of The 8Th Telegram - ABB A43 User Manual

Hide thumbs Also See for A43:
Table of Contents

Advertisement

Communication with M-Bus
Byte No.
148
149
150-155
156
157
158
159
160
161
162
163
164
165-170
171
172
173
174
175
176
177
178
179
180-185
186
187
188
10.3.8 Example of the 8th telegram (all values are hexadecimal
This example telegram contains the most recent snapshot of previous values.
Byte No.
1
2
3
4
5
6
7
8-11
12-13
14
15
2CMC48001M0201
Revision: C
Size
Value
1
81
1
xx
6
xxxxxxxxxxxx
1
8E
1
80
1
80
1
80
1
40
1
84
1
FF
1
82
1
xx
6
xxxxxxxxxxxx
1
8E
1
80
1
80
1
80
1
40
1
84
1
FF
1
83
1
xx
6
xxxxxxxxxxxx
1
1F
1
xx
1
16
Size
Value
1
68
1
DE
1
DE
1
68
1
08
1
xx
1
72
4
xxxxxxxx
2
4204
1
02
1
02
223
Description
VIFE L1
VIFE status
Apparent net energy, L1
DIF size, 12 digit BCD
DIFE
DIFE
DIFE
DIFE, Unit 8
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L2
VIFE status
Apparent net energy, L2
DIF size, 12 digit BCD
DIFE
DIFE
DIFE
DIFE, Unit 8
VIF for unit kVAh with resolution 0,01kVAh
VIFE next byte is manufacturer specific
VIFE L3
VIFE status
Apparent net energy, L3
DIF, more records will follow in next telegram
CS checksum, calculated from C field to last data
Stop character
Description
Start character
L-field, calculated from C field to last user data
L-field, repeated
Start character
C-field, RSP_UD
A-field, address
CI-field, variable data respond, LSB first
Identification Number, 8 BCD digits
Manufacturer: ABB
Version
Medium, 02 = Electricity
A43/A44
User Manual

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

A44

Table of Contents