Configuring The Meter - ABB A43 User Manual

Hide thumbs Also See for A43:
Table of Contents

Advertisement

Installation
Step
8
9
10
11
Use the information in this table to select the correct fuse for the circuit protec-tion.
Circuit protection
Table: 2:1
Meter type
Direct connected
Transformer connected

2.3.1 Configuring the meter

Default settings
For information about how to change the default settings of the meter, refer to the
chapter called Meter Settings.
Default settings
The following table lists the default settings of the meter that normally need to be
changed. Check the settings of the meter to see if they need to be reconfigured.
Parameter
Clock
Ratios VT
Ratios CT
Number of wires
Pulse frequency
Pulse length
A43/A44
User Manual
Action
Check that the meter is connected to the specified voltage and that voltage
phase connections and the neutral (if used) are connected to the correct termi-
nals.
For a transformer connected meter, check that the current direction of the pri-
mary and secondary current of the external transformers is correct. Also check
that the transformers are connected to the correct meter terminals.
Switch on the power. If a warning symbol is displayed, refer to the error codes
in Troubleshooting.
Under the menu item "Instantaneous Values" on the meter, check that the volt-
ages, currents, power and power factors are reasonable and that the power
direction is what to be expected (the total power should be positive for a load
that consumes energy). When doing the check the meter should be connected
to the intended load, preferably a load with a current above zero on all phases
to make the check as complete as possible.
Max circuit protection
80 A MCB, C characteristic or 80 A fuse type gL-gG
10 A MCB, B characteristic or Diazed, fast.
Direct connected meters
---
---
---
4
100 impulses / kWh (kvarh)
100 ms
20
Transformer connected meters
---
1/1
5/5
4
10 impulses / kWh (kvarh)
100 ms
2CMC48001M0201
Revision: C