Communication with M-Bus
Byte No.
Size
Value
115
1
FF
116
1
CA
117
1
FA
118
1
81
119
1
xx
120-121
2
xxxx
122
1
02
123
1
FF
124
1
CA
125
1
FF
126
1
82
127
1
xx
128-129
2
xxxx
130
1
02
131
1
FF
132
1
CA
133
1
FF
134
1
83
135
1
xx
136-137
2
xxxx
138
1
8E
139
1
80
140
1
40
141
1
84
142
1
xx
143-148
6
xxxxxxxxxxxx
149
1
8E
150
1
90
151
1
40
152
1
84
153
1
xx
154-159
6
xxxxxxxxxxxx
160
1
8E
161
1
A0
162
1
40
163
1
84
164
1
xx
165-170
6
xxxxxxxxxxxx
171
1
8E
172
1
B0
173
1
40
A43/A44
User Manual
Description
VIF next byte is manufacturer specific
VIFE phase angle current with resolution 0.1
VIFE next byte is manufacturer specific
VIFE L1
VIFE status
Phase angle current, L1
DIF size, 16 bit integer
VIF next byte is manufacturer specific
VIFE phase angle current with resolution 0.1
VIFE next byte is manufacturer specific
VIFE L2
VIFE status
Phase angle current, L2
DIF size, 16 bit integer
VIF next byte is manufacturer specific
VIFE phase angle current with resolution 0.1
VIFE next byte is manufacturer specific
VIFE L3
VIFE status
Phase angle current, L3
DIF size, 12 digit BCD
DIFE,
DIFE, unit 2
VIF for units kvarh with resolution 0,01kvarh
VIFE status
Reactive imported energy, Total
DIF size, 12 digit BCD
DIFE, tariff 1
DIFE, unit 2
VIF for units kvarh with resolution 0,01kvarh
VIFE status
Reactive imported energy, Tariff 1
DIF size, 12 digit BCD
DIFE, tariff 2
DIFE, unit 2
VIF for units kvarh with resolution 0,01kvarh
VIFE status
Reactive imported energy, Tariff 2
DIF size, 12 digit BCD
DIFE, tariff 3
DIFE, unit 2
208
2CMC48001M0201
Revision: C