Communication with M-Bus
0E ED EB 00 00 28 00 16 08 14 ;Date/time stamp for minimum given
above: 16:th of august 2014, 00:28:00 (hour:minute:second)
94 80 40 A9 FF F9 D9 00 70 08 00 00 ;Current demand (storage number 0)
for 1:st maximum sliding total reactive power import, VIF A9 -> data in
var with 2 decimals. Data = 00000870 hex = 21.60 var
0E ED EB 00 00 42 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:42:00
94 80 40 A9 FF F9 DA 00 80 07 00 00 ;Current demand (storage number 0)
for 2:nd maximum sliding total reactive power import, Data = 00000780
hex = 19.20 var
0E ED EB 00 00 41 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:41:00
94 80 40 A9 FF F9 DB 00 78 06 00 00;Current demand (storage number 0) for
3:rd maximum sliding total reactive power import, Data = 00000678 hex =
16.56 var
0E ED EB 00 00 40 00 16 08 14 ;Date/time stamp for maximum given
above: 16:th of august 2014, 00:40:00
A4 80 40 A9 FF F9 D1 00 00 00 00 00 ;Current demand (storage number 0)
for 1:st minimum total reactive power import, Data = 0 var
0E ED EB 00 00 15 00 16 08 14 ;Date/time stamp for minimum given
above: 16:th of august 2014, 00:15:00
0E ED EB FF F0 00 04 42 00 16 08 14 ;Date/time stamp for end of
measurement period. Will always be current date and time for the
currently pending period, in this case 16:th of august 2014, 00:42:04
1F ;Dif 1F -> More data exists
13 16 ;Checksum and stop byte
System sends out request UD2:
10 5B FE 59 16
Meter sends out data telegram 2:
68 C6 C6 68 08 00 72 34 12 00 00 42 04 20 02 B3 00 00 00 ;Data header
01 FD A5 00 0F ;Interval length 15 minutes
01 FF AB 00 01 ;Subinterval length 1 minute
94 80 80 40 A9 FF F9 D1 00 34 35 00 00 ;Current demand (storage
number 0) for 1:st maximum total apparent power import, VIF A9 -> data
in VA with 2 decimals. Data = 00003534 hex = 136.20 VA
A43/A44