Technical Description
The accuracy of the current harmonics varies with the harmonic amplitude and is
Accuracy
valid only provided there is no harmonics above the 20th harmonic.
Harmonic
Number
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
* For distortion levels below 1% the absolute uncertainty is ± 0.5%.
2CMC48001M0201
Revision: C
1% <
5% <
Distortion ≤ Distortion ≤
5%
10%
± 0.5%*
± 1.0
± 0.7%*
± 1.5%
± 1.0%
± 2.0%
± 1.2%
± 2.5%
± 1.5%
± 3.0%
±1.7%
± 3.5%
± 2.0%
± 4.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
± 2.5%
± 5.0%
53
10% <
20% <
Distortion ≤ Distortion ≤
20%
50%
± 2%
± 4%
± 3%
± 6%
± 4%
± 8%
± 5%
± 10%
± 6%
± 12%
± 7%
± 14%
± 8%
± 16%
± 10%
± 20%
± 10%
± 20%
± 10%
± 20%
± 10%
± 20%
± 10%
± 20%
± 10%
± 20%
± 10%
± 20%
± 10%
± 20%
50% <
Distortion ≤
100%
± 6%
± 9%
± 12%
± 15%
± 18%
± 21%
± 24%
± 30%
± 30%
± 30%
± 30%
± 30%
± 30%
± 30%
± 30%
A43/A44