Communication with Modbus
Quantity
3-Phase Sys. Power Factor
Power Factor L1
Power Factor L2
Power Factor L3
3-Phase Sys. Apparent Power
Apparent Power L1
Apparent Power L2
Apparent Power L3
3-Phase Sys. Active Power
Active Power L1
Active Power L2
Active Power L3
3-Phase Reactive power
Reactive Power L1
Reactive power L2
Reactive Power L3
3-Phase Sys. Active energy
3-Phase Sys. Reactive energy
Frequency
Current transformer ratio (current 11A0
transformer ratio secondary
current must be set to 1)
Voltage transformer ratio
(voltage transformer ratio
secondary voltage must be set to
1)
A43/A44
User Manual
Start Reg (Hex)
Size
1016
2
1018
2
101A
2
101C
2
1026
2
1028
2
102A
2
102C
2
102E
2
1030
2
1032
2
1034
2
1036
2
1038
2
103A
2
103C
2
103E
2
1040
2
1046
2
2
11A2
2
118
Unit
Data type
*1000
Signed
*1000
Signed
*1000
Signed
*1000
Signed
VA
Unsigned
VA
Unsigned
VA
Unsigned
VA
Unsigned
Watt
Signed
Watt
Signed
Watt
Signed
Watt
Signed
VAr
Signed
VAr
Signed
VAr
Signed
VAr
Signed
Wh*100
Unsigned
VArh*100
Unsigned
mHz
Unsigned
1-999999
Unsigned
1-9999
Unsigned
2CMC48001M0201