Example Of The 5Th Telegram (All Values Are Hexadecimal) - ABB A43 User Manual

Hide thumbs Also See for A43:
Table of Contents

Advertisement

Communication with M-Bus

10.3.5 Example of the 5th telegram (all values are hexadecimal)

Byte No.
1
2
3
4
5
6
7
8-11
12-13
14
15
16
17
18-19
20
21
22
23
24
25-30
31
32
33
34
35
36
37-42
43
44
45
46
47
48
49
50-55
56
57
58
59
60
A43/A44
User Manual
Size
Value
1
68
1
A4
1
A4
1
68
1
08
1
xx
1
72
4
xxxxxxxx
2
4204
1
02
1
02
1
xx
1
xx
2
0000
1
0E
1
84
1
FF
1
F2
1
xx
6
xxxxxxxxxxxx
1
8E
1
40
1
84
1
FF
1
F2
1
xx
6
xxxxxxxxxxxx
1
8E
1
80
1
40
1
84
1
FF
1
F2
1
xx
6
xxxxxxxxxxxx
1
8E
1
C0
1
40
1
84
1
FF
214
Description
Start character
L-field, calculated from C field to last user data
L-field, repeated
Start character
C-field, RSP_UD
A-field, address
CI-field, variable data respond, LSB first
Identification Number, 8 BCD digits
Manufacturer: ABB
Version
Medium, 02 = Electricity
Number of accesses
Status
Signature (0000 = no encryption)
DIF size, 12 digit BCD
VIF for units kWh with resolution 0,01kWh
VIFE next byte is manufacturer specific
VIFE resettable energy
VIFE status
Resettable active imported energy, Total
DIF size, 12 digit BCD
DIFE (Unit = 1)
VIF for units kWh with resolution 0,01kWh
VIFE next byte is manufacturer specific
VIFE resettable energy
VIFE status
Resettable active exported energy, Total
DIF size, 12 digit BCD
DIFE
DIFE (Unit = 2)
VIF for units kvarh with resolution 0,01kvarh
VIFE next byte is manufacturer specific
VIFE resettable energy
VIFE status
Resettable reactive imported energy, Total
DIF size, 12 digit BCD
DIFE (Unit = 1)
DIFE (Unit = 2)
VIF for units kvar with resolution 0,01kvarh
VIFE next byte is manufacturer specific
2CMC48001M0201