MERLIN NX IP AND MST/TP VAV CONTROLLER - INSTALLATION INSTRUCTIONS
SSR (DO) Wiring Examples
SR1 - SR5 Solid State Relay (SSR)
NOTE:
• SR IN (terminal 5, SSR power input) is connected to AC OUT (terminal 4, 24VAC~ output) by a jumper wire at fac-
tory.
• Remove the jumper if different voltages need to be used for SSRs.
• All terminals are protected against short circuit and 24VAC.
20 VDC Auxiliary Wiring Examples
EN1Z-1076GE51 R0722
UL Listed Class 2
Transformer
120 /
240 VAC
100 VA
Earth
Ground
SSR Wiring A With Separate Transformer Without Jumper Installed
UL Listed Class 2
Transformer
120 /
240 VAC
100 VA
Earth
Ground
WHEN CONNECTING POWER TO THE MERLIN IP/MSTP VAV CONTROLLERS,
1
CONNECT THE COM LEG OF THE VAC SECONDARY CIRCUIT TO A KNOWN EARTH GROUND.
Fig. 19 SSR (DO) Wiring Examples
20 VDC Auxiliary
Power Output
Fig. 20. 20 VDC Auxiliary Wiring
18
SSR Wiring With One Transformer And Factory Jumper