Soft Starter Specification - Mitsubishi Electric MEsoftstart/I01 Users, Installation & Instruction Manual

Table of Contents

Advertisement

Soft starter specification

Parameter
Supply Voltage
Current Ratings
Max. continuous current @ +50°C
Mitsubishi Electric Bypass contactor
Max continuous current with bypass
Max. starting current – normal duty
Max. starting current – heavy duty
Operating temperature
Storage temperature
Relative humidity
Operating altitude
Enclosure protection category
Communication
Standard on all variants
Pro variants only
Digital IO
Temperature Measurement inputs
Fault indication
Mounting
Module physical data (with finger guards)
Size WxHxD [mm] – no bypass
– with internal bypass
Weight – no bypass
– with internal bypass
Approximate heat loss
(without bypass at maximum rated current)
Insulation resistance
Current sensors
Rated frequency range
Quantity
Measurement dynamic range
Thermal rating
Accuracy
Sampling frequency
Voltage sensor
Rated frequency range
Quantity
Maximum rated voltage
Thermal rating
Accuracy
Sampling frequency
CE mark compliance
Standards applied (relevant sections)
*1 – Normal duty is for up to 10 starts per hour and start-up time no more than 30 seconds.
*2 – Heavy duty is for more than 10 starts per hour or start-up time longer than 30 seconds.
111 Specifications
Specification
340 – 420Vac, 425 – 578Vac, 586 -760Vac
MEsoftstart/I00
MEsoftstart/I01
100A
200A
S-T80
S-N150
120A
200A
240A
480A
125A
250A
-10°C - +60°C. De-rate all Ampere values at 1.4% per °C for temperatures >50°C
-30°C - +70°C
< 85%
1400m above sea-level (no derating). De-rate at 0.7% per 100m for altitudes >1400m
IP00
Modbus RTU (RS485, Baud rate: 9600- 115200) Default=115200, 1 start, 1 stop, even parity.
Modbus TCP (Ethernet 10BASE-TX / 100BASE-TX)
Core-variants
3 relay outputs (5A, 240Vac, pot.
free): READY, BYPASS, FAULT
3 inputs included: RUN/STOP,
RESET, Auto/Maintenance
PT-100 or LM35 motor temperature measurement channels (sensors purchasable separately)
Displayed on the TFT touch screen on Pro variants / flashing LED sequences on Core variants
Chassis mounted (see dimensions)
MEsoftstart/I00
MEsoftstart/I01
320x515x319
320x515x319
320x515x319
375x515x319
12kg
18kg
16kg
25kg
450W
650W
Dielectric breakdown voltage: 2kV
45Hz - 65Hz
3 (Hall effect on MEsoftstart/I00 and /I01, CTs on models MEsoftstart/I02 through /I04)
0% - 100% of soft starter maximum starting current – normal duty
Continuous: 2.5x rated current
1.0% of full scale
16.6kHz
45Hz - 65Hz
3 (direct sense by resistor bridge)
760Vac
800Vrms
1% of full scale
16.6kHz
Low voltage directive (2014/35/EU)
EMC directive (2014/30/EU)
RoHS 2 (2011/65/EU)
IEC/EN 60947-1
IEC/EN 60947-4-2
MEsoftstart/I02
MEsoftstart/I03
390A
600A
S-N400
S-N600
450A
800A
730A
1440A
390A
750A
Pro variants
8 relay outputs included (5A, 240Vac, pot. free): READY;
RUNNING; TRIP; BYPASS CONTACTOR; OVERLOAD
ALARM; FAULT / LINE VOLTAGE ALARM; TEMPERATURE
FAULT
3 inputs included: RUN/STOP; Auto/Maintenance;
RESET.
MEsoftstart/I02
MEsoftstart/I03
430x677x324
522x662x320
665x677x324
842x605x319
22kg
40kg
49kg
67kg
780W
1670W
MEsoftstart/I04
900A
(S-N800)
1000A
1600A
900A
MEsoftstart/I04
980x586x320
-
60kg
-
3410W

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents