Mitsubishi Electric MEsoftstart/I01 Users, Installation & Instruction Manual page 67

Table of Contents

Advertisement

Reference
Parameter group
6.4.7
Supply Tolerances
6.4.8
General Setup
6.4.9
Communication Setup
Basic Setup – Motor Hardware
The parameters that can be configured under this group are:
67 Basic operation – Pro models
Parameters
Factory Default (where applicable)
Max Volt Imbalance = 20%
Max Current Imbalance = 10%
Nominal Grid Voltage = 400V
Note that changing the nominal grid
voltage requires the installer to ensure
that all connected contactors (Bypass
etc) have their coils updated to the
same voltage level or damage to the
coils will ensue
User Language = English
Motor Name = 'Motor1'
Local/Remote Mode = Local
Password Edit = 0 (disabled)
Fault / Incoming CB = Fault
RS485 Baudrate = 115200
RS485 Parity = Even
Modbus Slave Address = 1
TCP/IP Parameters
Own IP address = 192.168.0.15
IP subnet mask = 255.255.255.0
Client IP address = 192.168.0.16
Gateway address = 192.168.0.1