Figure 34 – MEsoftstart/I Core – Start, Stop and Reset control options from the green wiring terminals
Note that (when in Auto control) the motor can be started from any of the three control inputs and stopped from any of the
three control inputs.
Example: If the motor is started from a remote controller by closing the switch on the green terminal and then the motor is
stopped by pushing the START/STOP button on the HMI panel, the motor will be stopped and can only be started again from the
remote controller after the switch is opened and then closed again.
If work needs to be done on the motor or the load, ensure that the Main supply is switched off to prevent inadvertent
starting from a remote switch or Modbus Master.
If an error occurs the motor will be stopped and the ERROR LED will be flashing to indicate the cause of the fault - refer paragraph
5.4. Once the cause of the fault is understood and removed, the soft starter will have to be RESET before operation can continue.
RESET can be done from the HMI panel, the Modbus RTU controller or a remote controller on the green terminal.
Jog
The 'Jog' functionality is available to slowly crawl a motor and its load to e.g. align a conveyor with a loading bay. Jog can be
configured and controlled from the HMI panel, as shown in Figure 35.
55 Basic operation – Core models