Parameters

This section explains configurable parameters. Parameters can be viewed and changed when the user selects to 'Configure the soft
starter' and then selects 'User Configure' (refer Figure 37). A menu will be presented allowing the user to configure the soft starter
as shown below.
Reference
Parameter group
6.4.1
Basic Setup – Motor
Hardware
6.4.2
Basic Setup – Start Setup
6.4.3
Basic Setup – Stop Setup
65 Basic operation – Pro models
Table 18: Configurable parameters of the soft starter

Parameters

Factory Default (where applicable)
Inside Delta = No
Workload Norm/Heavy = Normal
Bypass Contactor = Absent
Motor Size kW (depends on frame size)
Motor Application = Default
Phase Rotation = Clockwise
Protection Class = 10
RPM Sensor Presence = No
Start Type = Ramp
Ramp Type = Linear Time
Ramp Up Time = 10s
Maximum Starting Time = 60s (Normal
Duty) or unlimited (30minutes - Heavy
Duty)
Stop Type = Coasting
Ramp Down Time = 10s