Wiring terminals on the Pro variants
This section defines the wiring terminals on the full-featured MEsoftstart/I pro range of soft starters.
Wiring terminal X1 (Pro) – Control outputs
The green wiring terminal X1 on the bottom side of the soft starter (refer Figure 19) provides access to the control outputs of
the soft starter.
Terminal
Terminal name
X1-1
Ready-Relay
X1-2
Ready_Relay return
X1-3
Run-Relay
X1-4
Run_Relay return
X1-5
Shunt Trip Relay
X1-6
Shunt Trip Relay return
X1-7
Phase A
X1-8
Phase B
X1-9
Sensor-GND
X1-10
Not Connected
38 Wiring
Table 12: Control output wiring terminals on the Pro models
Terminal function description
This output signal from the soft starter will be active when the soft starter is ready to start the motor. It
may be used for a remote device to be able to start the motor. The signal will be inactive when configuring
the soft starter and while the motor is starting, running, stopping or the delay between starts is
implemented.
This output signal from the soft starter will be active when the soft starter is busy starting, running or stopping
the motor. It may be used to monitor the operation of the soft starter.
This output signal from the soft starter will be active whenever an internal stack over current is detected.
These input signals to the soft starter are used to be able to connect a shaft sensor to measure the motor's
revolutions per minute.
The MEsoftstart soft starter is not delivered with a shaft sensor. A compatible shaft sensor may be ordered
with the soft starter.
-
Figure 24 – Terminal X1 (Pro) – wiring example