3 Error Tables
Event code
Event name
5401544A hex
Instruction Execu-
tion Error Caused
by Count Mode
Setting
5401544C hex
Parameter Selec-
tion Out of Range
5401544D hex
Stop Method
Selection Out of
Range
5401544E hex
Latch ID Selection
Out of Range for
Trigger Input Con-
dition
5401544F hex
Setting Out of
Range for Writing
MC Setting
54015450 hex
Trigger Input Con-
dition Mode Selec-
tion Out of Range
54015451 hex
Drive Trigger Sig-
nal Selection Out
of Range for Trig-
ger Input Condition
54015453 hex
Motion Control
Instruction Re-exe-
cution Disabled
(Axis Specification)
54015454 hex
Motion Control
Instruction Re-exe-
cution Disabled
(Buffer Mode
Selection)
54015455 hex
Motion Control
Instruction Re-exe-
cution Disabled
(Direction Selec-
tion)
3-32
Meaning
An instruction that cannot
• An instruction that
be used when the Count
Mode is set to Rotary Mode
was executed for an axis
that was set to Rotary
Mode.
The parameter specified for
• Instruction input
the ParameterNumber
input variable to a motion
control instruction is out of
range.
The parameter specified for
• Instruction input
the StopMode input vari-
able to a motion control
instruction is out of range.
The parameter specified for
• Instruction input
the TriggerInput::LatchID
input variable to a motion
control instruction is out of
range.
The parameter specified for
• Instruction input
the SettingValue input vari-
able to a motion control
instruction is out of range.
• The parameter specifi-
The parameter specified for
• Instruction input
the TriggerInput:: Mode
input variable to a motion
control instruction is out of
range.
The parameter specified for
• Instruction input
the TriggerInput::Input-
Drive input variable to a
motion control instruction is
out of range.
An attempt was made to
• A parameter for an
change the parameter for
the Axis input variable
when re-executing a motion
control instruction. (This
input variable cannot be
changed when re-executing
an instruction.)
An attempt was made to
• A parameter for an
change the parameter for
the BufferMode input vari-
able when re-executing a
motion control instruction.
(This input variable cannot
be changed when re-exe-
cuting an instruction.)
An attempt was made to
• An input variable that
change the parameter for
the Direction input variable
when re-executing a motion
control instruction. (This
input variable cannot be
changed when re-executing
an instruction.)
Assumed cause
Maj
Prt
cannot be used when
the Count Mode is set
to Rotary Mode was
executed for an axis
that was set to Rotary
Mode.
parameter exceeded
the valid range of the
input variable.
parameter exceeded
the valid range of the
input variable.
parameter exceeded
the valid range of the
input variable.
parameter exceeded
the valid range of the
input variable.
cation and the data
type of the setting
value do not agree.
parameter exceeded
the valid range of the
input variable.
parameter exceeded
the valid range of the
input variable.
input variable that can-
not be changed for re-
execution was
changed.
input variable that can-
not be changed for re-
execution was
changed.
cannot be changed for
re-execution was
changed.
NJ-series Troubleshooting Manual (W503)
Level
Refer-
ence
Min
Obs
Info
S
NJ-series
Instruc-
tions Ref-
erence
Manual
(Cat. No.
W502)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.