Omron NJ Series Troubleshooting Manual page 150

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

3 Error Tables
NX-series EtherCAT Coupler Units
The section provides a table of the errors (events) that can occur in the following Unit.
NX-ECC201
Event code
Event name
00210000 hex
Bus Control-
ler Error
00220000 hex
Non-volatile
Memory
Hardware
Error
05010000 hex
ESC Error
05020000 hex
ESC Initial-
ization Error
05030000 hex
Slave Unit
Verification
Error
10420000 hex
Non-volatile
Memory Con-
trol Parame-
ter Error
10430000 hex
Memory Cor-
ruption
Detected
24A00000 hex
Unit Configu-
ration Error,
Too Many
Units
24A10000 hex
Unit Configu-
ration Error,
Unsupported
Configuration
35000000 hex
Unit Configu-
ration Infor-
mation Error
3-88
Meaning
Assumed cause
An internal bus
• A Unit failed or an I/O communi-
error occurred.
cations error occurred between
the EtherCAT Coupler Unit and
the NX Unit.
An error occurred in
• Non-volatile memory failure
non-volatile mem-
ory.
An error occurred in
• An error occurred in the Ether-
the EtherCAT slave
CAT slave communications
communications
controller.
controller.
Initialization of the
• An initialization error occurred
EtherCAT slave
in the EtherCAT slave commu-
communications
nications controller.
controller failed.
An error occurred in
• An error occurred in Slave Unit
Slave Unit verifica-
information.
tion.
An error occurred in
• The power supply to an NX Unit
the control parame-
was turned OFF or Sysmac
ters.
Studio communications were
disconnected while writing the
control parameters.
Memory corruption
• Memory corruption was
was detected.
detected.
The number of con-
• More than the maximum num-
nected NX Units
ber of NX Units is connected to
exceeds the maxi-
the EtherCAT Coupler Unit.
mum value for the
EtherCAT Coupler
Unit.
An unsupported NX
• An unsupported NX Unit was
Unit is mounted. Or,
detected.
the total byte size of
• The total byte size of all I/O
all I/O data for the
data for the connected NX Units
connected NX Units
exceeds 1,024 bytes for input
exceeds the prede-
data or 1,024 bytes for output
termined maximum
data.
value for the Ether-
CAT Coupler Unit.
An error occurred in
• The power supply to the Ether-
the Unit configura-
CAT Coupler Unit was turned
tion information in
OFF or Sysmac Studio commu-
the EtherCAT Cou-
nications were disconnected
pler Unit.
while downloading the Unit con-
figuration information.
Level
Maj
Prt
Min
Obs Info
S
NX-series
EtherCAT
Coupler Unit
User's Manual
(W519)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
NJ-series Troubleshooting Manual (W503)