Omron NJ Series Troubleshooting Manual page 153

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

Event code
Event name
85030000 hex
Communica-
tions Syn-
chronization
Error
84C50000 hex
NX Unit
Startup Error
35030000 hex
NX Unit
Observation
350E 0000 hex
NX Bus
Cycle Delay
Detected
80220000 hex
NX Message
Communica-
tions Error
90400000 hex
Event Log
Cleared
90420000 hex
Restart Exe-
cuted
90430000 hex
Memory All
Cleared
94600000 hex
I/O Check
Execution
Started
NX-series Digital I/O Units
The section provides a table of the errors (events) that can occur in the following Units.
NX-ID@@@@
NX-OC@@@@
NX-OD@@@@
Event code
Event name
00200000 hex
Non-volatile
Memory
Hardware
Error
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
The number of
• Power to the host controller was
consecutive errors
interrupted during process data
in receiving the
communications.
synchronization
• The EtherCAT communications
data exceeded the
cable is disconnected or bro-
value that is
ken.
specified in the
Communications
Error Settings.
Starting an NX Unit
• A startup error occurred in an
failed.
NX Unit.
An observation was
• An observation level error
detected in an NX
occurred in a Unit where an
Unit.
error was detected.
This event is recorded in the
event log in the Communica-
tions Coupler Unit.
Exceeding the NX
• The NX bus cycle was
bus cycle was
exceeded.
detected.
An error was
• The message communications
detected in mes-
load is high.
sage communica-
• The communications cable is
tions and the
disconnected or broken.
message frame
This cause does not apply if
was discarded.
attached information 2 is 0 (NX
bus).
• Message communications were
cut off as the result of executing
a synchronization or restora-
tion operation on the Sysmac
Studio or as the result of dis-
connecting an EtherCAT slave.
The event log was
• The event log was cleared by
cleared.
the user.
A restart was exe-
• A restart command was
cuted.
received.
The Unit settings
• The non-volatile memory in the
were cleared.
EtherCAT Coupler Unit was
cleared.
I/O checking was
• I/O checking was started.
started.
Meaning
Assumed cause
An error occurred in
• Non-volatile memory failure
non-volatile mem-
ory.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
NX-series
EtherCAT
Coupler Unit
User's Manual
(W519)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
Level
Maj
Prt
Min
Obs
Info
S
NX-series Dig-
ital I/O Units
User's Manual
(W521)
Reference
3
Reference
3-91