Omron NJ Series Troubleshooting Manual page 208

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

3 Error Tables
Event code
Event name
34AB0000 hex
Basic Ether-
net Setting
Error
34AC0000 hex
IP Address
Table Error
34AD0000 hex IP Router
Table Error
34AE 0000 hex
Routing Table
Error
34AF 0000 hex
Ethernet
Advanced
Setting Error
34B00000 hex
Address Mis-
match
381C 0000 hex
Status Area
Layout Set-
ting Error
54AE 0000 hex
Multiple
Switches ON
Error
84E00000 hex
IP Address
Duplication
Error
3-146
Meaning
Assumed cause
There is an illegal
• The power was interrupted dur-
TCP/IP setting.
ing a download.
• A communications error
occurred during a download.
The IP address
• The power was interrupted dur-
table information is
ing a download.
incorrect.
• A communications error
occurred during a download.
The IP router table
• The power was interrupted dur-
information is incor-
ing a download.
rect.
• A communications error
occurred during a download.
The routing table
• The power was interrupted dur-
information is incor-
ing a download.
rect.
• A communications error
occurred during a download.
There is an illegal
• The power was interrupted dur-
FINS setting.
ing a download.
• A communications error
occurred during a download.
The host ID of the
• The IP address conversion
local IP address is
method is set to automatic gen-
inconsistent with
eration, but the host ID of the
the FINS node
local IP address is inconsistent
address. Or, the
with the FINS node address or
last segment of the
the last segment of the local IP
local IP address is
address is inconsistent with the
inconsistent with
setting on the node address
the setting on the
switch.
node address
switches.
An error occurred in
• There is an error in the layout
the layout setting of
settings of the EtherNet/IP Unit.
the EtherNet/IP
Unit.
More than one soft-
• More than one software switch
ware switch
changed to TRUE at the same
changed to TRUE
time. Or, another software
at the same time.
switch changed to TRUE before
processing was completed for a
previous software switch.
The same IP
• The IP address of the Ether-
address is used
Net/IP port is also used as the
more than once.
IP address of another node.
Level
Maj
Prt
Min
Obs Info
S
CJ-series Eth-
erNet/IP Units
Operation
Manual for NJ-
series CPU
Unit (Cat. No.
W495)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
U
Same as
above.
S
Same as
above.
NJ-series Troubleshooting Manual (W503)
Reference

Advertisement

Table of Contents
loading

Table of Contents