3 Error Tables
NX-series Safety Control Units
The following table lists the events that can occur for NX-series Safety Control Units with the following
model numbers.
NX-SL@@@@
NX-SI@@@@
NX-SO@@@@
 Safety CPU Units
Event code
Event name
05200000 hex
System Error
10500000 hex
NX Bus Com-
munications
Settings
Read Error
10510000 hex
Safety Appli-
cation Data
Read Error
10520000 hex
NX Bus Com-
munications
Settings and
Safety Appli-
cation Data
Mismatch
10530000 hex
Non-volatile
Memory
Access Error
35200000 hex
Safety Pro-
cess Data
Communica-
tions Not
Established
Error
55000000 hex
Division by
Zero
55010000 hex
Cast Error
55020000 hex
MUX Error
74A00000 hex
SF_Antivalen
t Error
3-102
Meaning
Assumed cause
A hardware error
• Hardware has failed.
was detected dur-
• A memory error occurred due
ing self-diagnosis of
to a transient cause, such as a
the hardware.
software error or excessive
noise.
There is an error in
• A hardware failure occurred in
the NX bus commu-
the non-volatile memory.
nications settings
• Power was turned OFF while
that are saved in
saving data to the non-volatile
non-volatile mem-
memory.
ory.
There is an error in
• A hardware failure occurred in
the safety applica-
the non-volatile memory.
tion data that is
• Power was turned OFF while
saved in non-vola-
saving data to the non-volatile
tile memory.
memory.
There is an error in
• The NX bus communications
the safety applica-
settings that were transferred to
tion data that is
the Safety CPU Unit do not
saved in non-vola-
match the safety application
tile memory.
data.
Reading/writing
Non-volatile memory failed.
non-volatile mem-
ory failed.
Safety process data
• The communications settings
communications
for safety process data are not
was not estab-
correct, the safety slave is not
lished with one or
in the correct status, etc.
more safety slaves.
• The safety slave for safety pro-
cess data communications is
not connected.
• The safety slave for safety pro-
cess data communications is
disabled.
Division by zero
The divisor is zero.
was detected.
A casting error was
A value was input that exceeded
detected.
the range of the receiving vari-
able.
An MUX instruction
The value of the selection input
error was detected.
(K) to the MUX instruction is not
correct.
An error was
Refer to information on the diag-
detected in execu-
nostic code that is given for
tion of a safety
attached information 1 in the NX-
function block.
series Safety Control Unit Instruc-
tions Reference Manual (Cat. No.
Z931)
Level
Maj
Prt
Min
Obs Info
S
NX-series
Safety Control
Unit User's
Manual (Z930)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
NJ-series Troubleshooting Manual (W503)