Omron NJ Series Troubleshooting Manual page 41

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

Always confirm safety at the connected equipment before you reset Controller errors for a CJ-
series Special Unit. When the Controller error is reset, the Unit where the Controller error with an
event level of observation or higher will be restarted. Before you reset all errors, confirm that no
Controller errors with an event level of observation or higher have occurred for the CJ-series
Special Unit. Observation level events do not appear on the Controller Error Tab Page, so it is
possible that you may restart the CJ-series Special Unit without intending to do so. You can
check the status of the _CJB_UnitErrSta[0,0] to _CJB_UnitErrSta[3,9] Error Status variables on
a Watch Tab Page to see if an observation level Controller error has occurred.
Precautions for Correct Use
Precautions for Correct Use
Resetting an error is not the same as eliminating the cause of the error. Always eliminate the
cause of an error before you perform the procedure to reset the error.
Error Resetting Methods
Method
Commands from
Sysmac Studio
Commands from an
*2
NS-series PT
NJ-series Troubleshooting Manual (W503)
Errors that are
Operation
reset
Resetting Controller
Resetting all errors
errors
in the entire Control-
ler
Resetting all Slave
Terminal errors
Resetting errors for
individually speci-
fied NX Units
Downloading
Resetting all errors
for a specific func-
tion module
Clear All Memory
Resetting all errors
for all function mod-
ules
Controller reset
Clear All Memory
Resetting all Slave
operation for Slave
Terminal errors
Terminal
Restarting the Slave
Terminal
Resetting Controller
Resetting all errors
errors
in the entire Control-
ler
1 Overview of Errors
Description
Reset the Controller errors from the Sys-
mac Studio's Troubleshooting Dialog Box.
Refer to the manual for the Communica-
tions Coupler Unit for details on resetting
errors in a Slave Terminal.
After the causes of the Controller errors are
removed, all Controller errors in the relevant
function module are reset as a result. Errors
are not reset when you download the Con-
troller Configurations and Setup.
After the causes of the Controller errors are
removed, all Controller errors in all function
modules are reset as a result. Errors for
Slave Terminals are not reset.
After the causes of the Controller errors are
removed, all Controller errors in all function
modules are reset as a result. Errors for
Slave Terminals are not reset.
If the causes for the Controller errors are
removed, all Controller errors in the Slave
Terminals are reset.
Reset Controller errors from the Trouble-
shooter of an NS-series PT that is compati-
ble with NJ-series Controllers.
You can reset errors from a PT that is not
directly compatible with the NJ-series Con-
troller or another company's HMI if you use
the PT/HMI in combination with the reset
error instruction for the function module in
the user program.
1
*1
*1
1-15