Omron NJ Series Troubleshooting Manual page 169

Sysmac machine automation controller
Hide thumbs Also See for NJ Series:
Table of Contents

Advertisement

Event code
Event name
65280000 hex
Stuck-at-high
Detected at
Safety Output
80200000 hex
NX Unit I/O
Communica-
tions Error
80300000 hex
Safety Pro-
cess Data
Communica-
tions Timeout
84F1 0000 hex
NX Bus I/O
Communica-
tions
Stopped
80220000 hex
NX Message
Communica-
tions Error
90400000 hex
Event Log
Cleared
90430000 hex
Memory All
Cleared
NJ-series Troubleshooting Manual (W503)
Meaning
Assumed cause
It was detected that
• The positive power supply line
the safety output
is in contact with the output sig-
terminal is stuck
nal line.
ON.
• The output power supply is out-
side the specifications.
• The internal circuit is faulty.
• A memory error or signal error
occurred due to a transient
cause, such as a software error
or excessive noise.
An I/O communica-
• The NX Unit is not mounted
tions error occurred
properly.
between the Com-
• There is a hardware error in the
munications Cou-
NX Unit.
pler Unit and the
NX Unit.
A communications
• A setting is not correct. The set-
timeout occurred in
ting of the safety task period of
safety process data
the Safety CPU Unit is too
communications
short. Or, the setting of the
with a safety slave.
PDO communications safety
task period of the EtherCAT
master is too short.
• There is excessive noise.
• The safety slave entered a sta-
tus where it could not continue
safety process data communi-
cations.
• An error or status change
occurred in the EtherCAT Cou-
pler Unit to which the Unit is
connected, preventing correct
process data communications.
An error occurred in
There is a hardware error in the
I/O communications
Communications Coupler Unit or
between the Com-
an NX Unit.
munications Cou-
pler Unit and an NX
Unit.
An error was
• The message communications
detected in mes-
load is high.
sage communica-
• The communications cable is
tions for an NX Unit
disconnected or broken.
and the message
frame was dis-
carded.
The event log was
The event log was cleared by the
cleared.
user.
The Unit settings
The Clear All Memory operation
were cleared.
was performed.
3 Error Tables
Level
Maj
Prt
Min
Obs
Info
S
NX-series
Safety Control
Unit User's
Manual (Z930)
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
S
Same as
above.
Reference
3
3-107