AEMC PowerPad 8436 User Manual page 88

3-phase power quality analyzer
Hide thumbs Also See for PowerPad 8436:
Table of Contents

Advertisement

Measurement
J93 clamp
SR193 clamp
MR193 clamp
MN93 clamp
SL261 clamp (10 mV/A)
MN193 clamp (100 A)
SL261 clamp (100
mV/A)
RMS ½
MN193 clamp (5 A)
current
5 A adapter
Essailec
®
AmpFlex
® (2)
MiniFlex
® (2)
(10 kA)
AmpFlex
® (2)
MiniFlex
® (2)
(6500 A)
AmpFlex
® (2)
MiniFlex
® (2)
(100 A)
J93 clamp
SR193 clamp
MR193 clamp
MN93 clamp
SL261 clamp (10 mV/A)
MN193 clamp (100 A)
SL261 clamp (100
mV/A)
Peak
MN193 clamp (5 A)
current (PK)
5 A adapter
Essailec
®
AmpFlex
® (2)
MiniFlex
® (2)
(10 kA)
AmpFlex
® (2)
MiniFlex
® (2)
(6500 A)
AmpFlex
® (2)
MiniFlex
® (2)
(100 A)
(1) 3500 x √2 ≈ 4,950; 1000 x √2 ≈ 1,414; 200 x √2 ≈ 282.8; 100 x √2 ≈ 141.4; 10 x √2 ≈ 14.14; 10,000 x √2 ≈ 14,140; 6,500 x √2 ≈ 9192
(2) Sensors compatible with the instrument (see §1.2).
Measurement range without
ratio (with unity ratio)
Minimum
1 A
1 A
200 mA
0.1A
10 mA
5 mA
adapter
10 A
10 A
100 mA
1 A
1 A
200 mA
100 mA
10 mA
5 mA
adapter
10 A
10 A
100 mA
Display resolution
(with unity ratio)
Maximum
3500 A
1 A
100 mA
A < 1000 A
1200 A
1 A
A ≥ 1000 A
240 A
100 mA
10 mA
A < 100 A
120 A
100 mA
A ≥ 100 A
1 mA
A < 10 A
12 A
10 mA
A ≥ 10 A
6 A
1 mA
1 A
A < 10 kA
10 kA
10 A
A ≥ 10 kA
100 mA
A < 1000 A
6500 A
1 A
A ≥ 1000 A
10 mA
A < 100 A
100 A
100 mA
A ≥ 100 A
4950 A
1 A
(1)
1 A
A < 1000 A
1414 A
(1)
1 A
A ≥ 1000 A
282.8 A
100 mA
(1)
10 mA
A < 100 A
141.4 A
(1)
100 mA
A ≥ 100 A
1 mA
A < 10 A
14.14 A
(1)
10 mA
A ≥ 10 A
7.071 A
1 mA
(1)
1 A
A < 10 kA
14.14 kA
(1)
10 A
A ≥ 10 kA
100 mA
A < 1000 A
9192 kA
(1)
1 A
A ≥ 1000 A
10 mA
A < 100 A
141.4 A
(1)
100 mA
A ≥ 100 A
88
Maximum intrinsic error
± (1% + 1 A)
±(1% + 1 A)
±(1% + 1 A)
±(1% + 100 mA)
±(1% + 10 mA)
±(1% + 10 mA)
±(2.5% + 5 A)
±(2.5% + 5 A)
±(2.5% + 200 mA)
±(1% + 2 A)
±(1% + 2 A)
±(1% + 2 A)
±(1% + 200 mA)
±(1% + 20 mA)
±(1% + 20 mA)
±(3 % + 5 A)
±(3% + 5 A)
±(3% + 600 mA)

Advertisement

Table of Contents
loading

Table of Contents