Description; Functions; Measurements - AEMC PowerPad 8436 User Manual

3-phase power quality analyzer
Hide thumbs Also See for PowerPad 8436:
Table of Contents

Advertisement

2.1. FUNCTIONS

The Model 8436 a three-phase network analyzer with color graphic display and built-in rechargeable battery. The instrument:
measures RMS values, powers, and perturbations of electric distribution networks
delivers a snapshot of the principal characteristics of a three-phase network
tracks variations of various parameters over time
provides IP67 (watertight) operation
The measurement uncertainty of the Model 8436 is better than 1% (excluding uncertainties due to connected sensors). The instrument
is also versatile, with a choice of sensors providing measurements ranging from a few mA (MN193) to several kA (AmpFlex
The instrument is compact and impact resistant, with a simple and easy-to-use interface. It is designed for technicians and engineers
performing electrical network installation, inspection and maintenance.

2.1.1. MEASUREMENTS

The Model 8436 measures:
RMS values of AC voltages up to 1000V between terminals. By using the ratios, the instrument can measure voltages up to
hundreds of gigavolts.
RMS values of AC currents up to 10,000A (neutral included). By using the ratios, the instrument can measure currents up to
hundreds of kiloamperes.
DC components of voltages and currents (neutral included).
Minimum and maximum half-cycle RMS voltage and current values (excluding neutral).
Peak voltage and current values (neutral included).
Frequency of 50Hz and 60Hz networks.
Current and voltage peak factors (neutral included).
Harmonic loss factor (FHL), application to transformers in the presence of harmonic currents.
K factor (FK), application to transformers in the presence of harmonic currents.
Total harmonic distortion with respect to the fundamental (THD in %f) of the current and of the voltages (excluding neutral).
Total harmonic distortion with respect to the RMS AC value (THD in %r) for the current and the voltages (neutral included).
Active, reactive (capacitive and inductive), non-active, distortion, and apparent power, by phase and cumulative (excluding
neutral).
Power factor (PF) and displacement factor (DPF) or cos Φ (excluding neutral).
RMS distortion value (d) for the current and the voltages (excluding neutral).
Short-term voltage flicker (PST) (excluding neutral).
Long-term voltage flicker (PLT) (excluding neutral).
Active, reactive (capacitive and inductive), non-active, distortion, and apparent energy (excluding neutral).
Current and voltage harmonics (excluding neutral) up to order 50: RMS value, percentage referred to the fundamental, (%f)
(excluding neutral), or the total RMS value (%r), minimum and maximum and sequence harmonics.
Apparent harmonic power up to order 50 (excluding neutral): percentages referred to the fundamental apparent power (%f) or
the total apparent power (%r), minimum and maximum of a rank.
Inrush currents, starting of motors.
2.

DESCRIPTION

10
).
®