VLT AQUA High Power Operation Instructions

2.1.9. IT Mains

Par. 14-50
ground. If this is done it will reduce the RFI performance to A2 level.
2.1.10. Software Version and Approvals: VLT AQUA Drive
This Operating Instructions can be used for all VLT AQUA Drive frequency converters with
software version 1.00.
The software version number can be seen from parameter 15-43.
2.1.11. Disposal Instruction
IT Mains
Do not connect 400 V frequency converters with RFI-filters to mains supplies with a
voltage between phase and earth of more than 440 V.
For IT mains and delta earth (grounded leg), mains voltage may exceed 440 V be-
tween phase and earth.
RFI 1
can be used to disconnect the internal RFI capacitiors from the RFI filter to
VLT AQUA Drive
Operating Instructions
Software version: 1.00
Equipment containing electrical components must not be disposed of
together with domestic waste.
It must be separately collected with electrical and electronic waste
according to local and currently valid legislation.
®
MG.20.P1.02 - VLT
is a registered Danfoss trademark