Parameter Object; Class Code 0X000F - Allen-Bradley ArmorStart 290E User Manual

Lt distributed motor controller
Table of Contents

Advertisement

Appendix B
CIP Information

Parameter Object

Attribute ID
Access Rule
1
Get
2
Get
8
Get
9
Get
Attribute ID
Access Rule
1
Get/Set
2
Get
3
Get
4
Get
5
Get
6
Get
7
Get
8
Get
9
Get
10
Get
11
Get
12
Get
13
Get
14
Get
15
Get
16
Get
212
The following common services will be implemented for the Analog Output
Point Object:
Service Code
0x0E
0x10

CLASS CODE 0x000F

The following class attributes will be supported for the Parameter Object:
Name
Revision
Max Instance
Parameter Class Descriptor
Configuration Assembly Instance
The number of instances of the parameter object will depend upon the type of
Distributed Starter that the control board is connected to.
The following instance attributes will be implemented for all parameter
attributes:
Name
Value
Specified in Descriptor
Link Path Size
USINT
Array of:
Link Path
Descriptor
WORD
Data Type
EPATH
Data Size
USINT
Parameter Name String
SHORT_STRING
Units String
SHORT_STRING
Help String
SHORT_STRING
Minimum Value
Specified in Descriptor
Maximum Value
Specified in Descriptor
Default Value
Specified in Descriptor
Scaling Multiplier
UINT
Scaling Divisor
UINT
Scaling Base
UINT
Scaling Offset
INT
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Implemented for:
Class
Instance
Yes
Yes
No
Yes
Data Type
UINT
UINT
WORD
UINT
Data Type
BYTE
EPATH
Service Name
Get_Attribute_Single
Set_Attribute_Single
Value
100 for Bulletin 290E/291E units
101 for Bulletin 294E units
Value

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Armorstart 291eArmorstart 294e

Table of Contents