Allen-Bradley ArmorStart 290E User Manual page 153

Lt distributed motor controller
Table of Contents

Advertisement

AutoRstrtDelay
Sets time between restart attempts when
Parameter 84(Auto Rstrt Tries) is set to a
value other than zero.
BoostSelect
Sets the boost voltage (% of Parameter 28
[MotorNPVolts]) and redefines the Volts
per Hz curve.
See Table 24 for details.
Table 24 - Boost Select Options
Options
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Bulletin 290E/291E/294E Programmable Parameters
Parameter Number
Related Parameter
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Related Parameters
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Description
Custom V/Hz
30.0, VT
35.0, VT
40.0, VT
45.0, VT
0.0 no IR
0.0
2.5, CT
5.0, CT (default)
7.5, CT
10.0, CT
12.5, CT
15.0, CT
17.5, CT
20.0, CT
Chapter 4
85
84
GET/SET
UINT
Advanced Config.
x.x secs
0.0
120.0
1.0
86
28, 29
GET/SET
UINT
Advanced Config.
1
14
8
Variable Torque
(Typical fan/pump curves)
Constant Torque
153

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Armorstart 291eArmorstart 294e