Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
148
Figure 54 - Skip Frequency Band
Frequency
Command
Frequency
Skip Frequency
DCBrakeTime
Sets the length of time that DC brake current is
injected into the motor. Refer to Parameter 76
(DCBrakeLevel).
DCBrakeLevel
Defines the maximum DC brake current, in amps,
applied to the motor when Parameter 32
(StopMode) is set to either
0 = RAMP or 2 = DC BRAKE.
For 0.5 Hp units – Min = 0; Max = 2.7; Default = .1
For 1.0 Hp units – Min = 0; Max = 4.5; Default = .1
For 2.0Hp units – Min = 0; Max = 7.5; Default = .2
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Drive Output
Frequency
Time
Parameter Number
Related Parameters
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Related Parameters
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
2x Skip
Frequency Band
75
32, 76
GET/SET
UINT
Advanced Config.
x.x secs
0.0
99.9
(Setting of 99.9 = Continuous)
0.0
76
32, 75
GET/SET
UINT
Advanced Config.
x.x Amps
0.0
Hp Dependant
Hp Dependant