Allen-Bradley ArmorStart 290E User Manual page 141

Lt distributed motor controller
Table of Contents

Advertisement

5
4
X
X
FilterOffOn
This parameter determines the input
(which must be present for this time)
before being reported ON.
FilterOnOff
This parameter determines the input
(which must be absent for this time)
before being reported OFF.
OutProtFltState
This parameter in conjunction with
Parameter 53 (OutProtFltValue) defines
how the starter outputs will respond
when a fault occurs.
0 = GoToPrFltValue
1 = IgnorePrFlt
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Bulletin 290E/291E/294E Programmable Parameters
Bit
3
2
1
X
X
X
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Chapter 4
Function
0
X
Pt00
Pt01
Pt02
Pt03
Pt04
Pt05
50
GET/SET
USINT
User I/O Config.
msecs
0
64
0
51
GET/SET
USINT
User I/O Config.
msecs
0
64
0
52
GET/SET
BOOL
User I/O Config.
0
1
0