Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
118
OutNetIdleValue
This parameter determines the state that
starter outputs assumes when the
network is idle and Parameter 56
(OutNetIdleState) is set to 0.
0 = OFF
1 = ON
Input00Function
This parameter determines the special
function for User Input 0:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive. All
others are edge sensitive
Input01Function
This parameter determines the special
function for User Input 1:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive. All
others are edge sensitive
Input02Function
This parameter determines the special
function for User Input 2:
0 = NoFunction
1 = FaultReset
2 = MotionDisable
3 = ForceSnapShot
4 = UserFault
5 = BrakeRelease
These choices are level sensitive. All
others are edge sensitive
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
57
GET
BOOL
User I/O Config.
0
1
0
58
GET/SET
USINT
User I/O Config.
0
4
0
59
GET/SET
USINT
User I/O Config.
0
4
0
60
GET/SET
USINT
User I/O Config.
0
4
0