Allen-Bradley ArmorStart 290E User Manual page 164

Lt distributed motor controller
Table of Contents

Advertisement

Chapter 5
Diagnostics
Blink
Auto-Reset
Pattern
Capable
Disable
7
Yes
No
8
Drive
No
Controlled
9
Drive
No
Controlled
10
Drive
No
Controlled
11
No
No
12
No
No
13
No
No
14
No
No
15
Yes
Yes
16
No
No
164
Table 29 - Fault LED Indicator for Bulletin 294E
Bulletin 294E
Default
Trip Status
On
Parameter Sync (PF
This fault is generated during the
4M Codes 48, 71
parameter synchronization procedure
and 81)
between the Control Module and the
internal drive when the syncing process
fails resulting in the drive configuration
not matching the Control Module
configuration.
On
DCBusOrDiscnnct
This fault is a result of the drive's Power
(PF 4M Codes 3, 4
Loss (PF 4M Code 3), UnderVoltage (PF 4M
and 5)
Code 4) and OverVoltage (PF 4M Code 5)
faults. When an Undervoltage occurs
because the Disconnect has been opened,
the condition will be diagnosed as an
"Open Disconnect" trip
On
Stall Trip
During starting the motor did not reach
(PF 4M Code 6)
running speed within the prescribed
period. This fault occurs when the drive
detects a motor stall condition during
acceleration.
On
Over Temperature
This fault occurs when the drive detects a
(PF 4M Code 8)
heat sink over temperature condition.
On
Ground Fault
This fault occurs a current path to earth
(PF 4M Code 13)
ground has been detected at one or more
of the drive output terminals.
On
Restart Retries
Drive unsuccessfully attempted to reset a
(PF 4M Code 33)
fault and resume running for the
programmed number of auto retries.
On
Drive Hardware Fault
Failure has been detected in the drive
power section.
On
Output Short
This fault is generated when a hardware
output short circuit condition is detected.
Off
User Defined
This fault is generated either in response
to the rising edge of user input 0...5,
[Input00Function...Input- 05Function]
Parameter 58...63.
On
Hardware Fault Trip
This fault indicates that a serious
hardware problem exists. This fault is
generated when either the PF 4M drive is
not detected or an invalid factory
configuration setting is detected.
In the case of a Disconnect open fault, reclosing the disconnect will cause a reset to be issued.
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Description
1. The most common cause of this fault is that the
disconnect has been opened, or that power has
been removed from the drive. To clear the fault,
repower the drive and activate a reset.
2. The drive may have been commanded to default
values. Clear the fault or cycle power to the drive.
1. The most common cause of this fault is that the
disconnect has been opened, or that power has
been removed from the drive. To Clear the fault,
repower the drive and activate a reset.
2. Monitor the incoming line for phase loss or line
imbalance, low voltage or line power interruption.
high line voltage or transient conditions. Bus
OverVoltage can also be caused by motor
regeneration.
3. Extending the [DecelTime1] Parameter 37 or
[DecelTime2] Parameter 70 may also help with this
fault.
1. Check for source of stall (for example, excessive
load, or mechanical transmission component
failure).
2. Increase [AccelTime1] Parameter 36 or
[AccelTime2] Parameter 69 or reduce load so drive
output current does not exceed the current set by
[CurrentLimit] Parameter 31.
Check for blocked or dirty heat sink fins. Verify that
ambient temperature has not exceeded 40° C (104° F).
Check the motor and external wiring to the drive
output terminals for a grounded condition.
Correct the cause of the fault and manually clear.
Check [AutoRestartTries] Parameter 84 and
[AutoRestartDelay] Parameter 85 meets application
needs.
1. Cycle power.
2. Replace unit if failure can not be cleared.
Correct, isolate or remove wiring error prior to
restarting the system.
This fault is generated based on user configuration.
This fault may be reset after the condition that caused
it is removed. For example, the Auxiliary Input goes
low or the DeviceLogix logic drives the bit low.
Power cycle to correct. If fault persists the ArmorStart
LT requires replacement.
Action