Allen-Bradley ArmorStart 290E User Manual page 96

Lt distributed motor controller
Table of Contents

Advertisement

Chapter 3
Product Commissioning
96
Table 21 - Bulletin 290E/291E Produced Assembly Status Tag Explanation
Device Input Status Tags
Fault
TripPresent
WarningPresent
RunningForward
RunningReverse
Ready
CurrentFlowing
DeviceLogixEnabled
KeypadAuto
KeypadOff
KeypadHand
DisconnectClosed
Pt00Data
Pt01Data
Pt02Data
Pt03Data
Pt04Data
Pt05Data
Pt00DeviceOut
Pt01DeviceOut
Pt02DeviceOut
Pt03DeviceOut
Pt04DeviceOut
Pt05DeviceOut
Pt06DeviceOut
Pt07DeviceOut
Pt08DeviceOut
Pt09DeviceOut
Pt10DeviceOut
Pt11DeviceOut
Pt12DeviceOut
Pt13DeviceOut
Pt14DeviceOut
Pt15DeviceOut
Int00DeviceOut
L1Current
L2Current
L3Current
AvgCurrent
PercentTCU
SwitchedVoltageLevel
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Tag Description/Use
Communication fault between PLC and device (all 1s = fault, all 0s = normal)
Fault exists within unit
Warning of potential fault
Motor commanded to run forward
Motor commanded to run reverse
Control and 3-phase power present
Current is passing to motor
DeviceLogix is enabled
HOA is in Auto mode
HOA is in Off mode
HOA is in Hand mode
Disconnect is closed
User-configured I/O status
User-configured I/O status
User-configured I/O status
User-configured I/O status
ASLT_DEMO:I.Pt04Data
User-configured I/O status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network output status
DeviceLogix network analog output
Phase A current
Phase B current
Phase C current
Average phase A, B, and C current
Overload percentage thermal utilization (100% = overload trip)
Switched control power voltage — Parameter 11