Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
152
AutoRstrtTries
Set the maximum number of times the drive
attempts to reset a fault and restart.
Clear a Type 1 Fault and Restart the Drive
1. Set Parameter 84 (AutoRestartTries) to a value other than 0.
2. Set Parameter 85 (AutoRestartDelay) to a value other than 0.
Clear an Overvoltage, Undervoltage, or Heatsink OvrTmp Fault without Restarting the Drive
1. Set Parameter 84 (AutoRestartTries) to a value other than 0.
2. Set Parameter 85 (AutoRestartDelay) to 0.
ATTENTION: Equipment damage and/or personal injury may result if this
parameter is used in an inappropriate application. Do not use this function
without considering applicable local, national, and international codes,
standards, regulations, or industry guidelines.
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Parameter Number
Related Parameter
Access Rule
Data Type
Group
Advanced Config.
Units
Minimum Value
Maximum Value
Default Value
84
85
GET/SET
UINT
0
9
0