Appendix C
Using DeviceLogix™
250
21. Expand the output tag of the ArmorStart LT, i.e.: Armorstart_LT_36:O
22. Enter the following value:
Name
Armorstart_LT_36:O.FreqCommand
Armorstart_LT_36_O.RunForward
23. Toggle the Armorstart_LT_36_O.RunForward to move the motor in the
forward direction. Then toggle Armorstart_LT_36_O.RunReverse. The
motor will run in the reverse direction.
24. Change the value of the FreqCommand to vary the speed.
Note: Setting the tag value to 500 instructs the drive to run at 50.0Hz
This example configuration is now complete. If additional help is needed, please
contact your Rockwell Automation sales representative or technical support.
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Value
Description
300
30.0Hz, Setting Target Frequency
1
Start the RUNning in Forward Direction