Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
142
OutProtFltValue
This parameter determines how the starter
outputs will be commanded in the event
of a protection fault if Parameter 52
(OutProtFltState) = 0.
0 = OFF
1 = ON
OutNetFaultState
This parameter in conjunction with
Parameter 55 (OutNetFaultValue) defines
how the starter outputs will respond
on an Ethernet fault.
0 = GoToFaultValue
1 = HoldLastState
OutNetFaultValue
This parameter determines the state that
starter outputs when an Ethernet fault
occurs and Parameter 54
(OutNetFaultState) is set to 0.
0 = OFF
1 = ON
OutNetIdleState
This parameter in conjunction with
Parameter 57 (OutNetIdleValue) defines
how the starter outputs will respond when
a network is idle.
0 = GoToIdleValue
1 = HoldLastState
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
53
GET/SET
BOOL
User I/O Config.
0
1
0
54
GET/SET
BOOL
User I/O Config.
0
1
0
55
GET
BOOL
User I/O Config.
0
1
0
56
GET/SET
BOOL
User I/O Config.
0
1
0