Allen-Bradley ArmorStart 290E User Manual page 168

Lt distributed motor controller
Table of Contents

Advertisement

Chapter 6
Specifications
Operating Temperature Range
Storage and Transportation Temperature Range
Pollution Degree
Enclosure Ratings
Approximate Shipping Weight
Resistance to Shock
Resistance to Vibration
Disconnect Lock Out
Disconnect LOTO Locks
Disconnect Mechanical Life
Contractor Utilization Category
(IEC)
Contactor Opening Delay
Contactor Closing Delay
Minimum Off Time
Contactor Mechanical Life
Wire Size
Wire Type
Tightening Torque
Wire Strip Length
Power Rating
Emission
Immunity
IP66/UL Type 4 is available with gland options G1-3. IP66/UL Type 4/12 available with G1 and G3 gland option
When two wires used in terminal block both wires are to be of same wire AWG.
168
Altitude
Humidity
Operational
Non-Operational
Operational
Non-Operational
Power Terminals
(2) #18 ...#10 AWG
2
(0.8...5.2 mm
) per terminal
(0.8...5.2 mm
10.6 ± 2 lb•in (1.2 ± 0.2 N•m)
600V AC/25 Amp
Emission and Immunity Ratings
Conducted
Radiated
Electrostatic Discharge
Radio Frequency Electromagnetic Field
Fast Transient
Surge Transient
Radio Frequency Conducted Disturbance
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Environmental Ratings
Mechanical Ratings
30 G, exceeds IEC 60947-1
50 G, exceeds IEC 60947-1
2.5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
5 G, tested to MIL-STD-810G, exceeds IEC 60947-1
Maximum of 3/8 in. (9.5 mm) diameter lock shackle or hasp
Up to 2 locks or hasps are supported
200 000 operations
AC-1, AC-3, AC-4 (refer to Life Load Curves)
8...12 ms
18...40 ms
200 ms
15 million operations
Motor Terminals
#18...#10 AWG
2
) per terminal
(0.8...5.2 mm
Multi-strand copper wire
0.35 ± 0.01 in. (9 ± 2 mm)
600 V AC/10 Amp
-20...+50 °C (-4...+122 °F)
-25...+85 °C (-13...+185 °F)
2000 m
5...95% (non-condensing)
3
IP66/UL Type 4/12
4.6 kg (10 lb)
Control Terminals
(2) #18 ...#10 AWG
(2) #16 ...#10 AWG
2
) per terminal
(1.3...5.2 mm
18 ± 2 lb•in (2 ± 0.2 N•m)
600 V AC/10 Amp
EN 60947-4-1
Class A
4 kV contact, 8 kV air
EN 60947-4-1
10V/m, 80 MHz...1 GHz
10V/m, 1.4 GHz...2 GHz
2 kV (Power)
2 kV (PE)
1 kV (Communication and control)
1 kV (12)
, 2 kV (2)
(earth)
L-L
L-N
10V, 150 kHz...80 MHz
PE/Ground
2
) per terminal

Hide quick links: