Allen-Bradley ArmorStart 290E User Manual page 122

Lt distributed motor controller
Table of Contents

Advertisement

Chapter 4
Bulletin 290E/291E/294E Programmable Parameters
122
JamWarningLevel
This parameter determines the Jam
Warning Level as a percentage
of Full Load Amps.
StallEnabledTime
This parameter determines the time
that stall detection is enabled during
motor starting.
StallTripLevel
This parameter determines the Stall Trip
Level as a percentage of Full Load Amps.
ULInhibitTime
This parameter determines the time
during motor starting that Underload
detection is inhibited.
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
73
GET
UINT
Advanced Config.
%FLA
50
600
150
74
GET
USINT
Advanced Config.
secs
0
250
10
75
GET
UINT
Advanced Config.
%FLA
100
600
600
76
GET
USINT
Advanced Config.
secs
0
250
10

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Armorstart 291eArmorstart 294e

Table of Contents