Allen-Bradley ArmorStart 290E User Manual page 167

Lt distributed motor controller
Table of Contents

Advertisement

Input
Output
Input ON-to-OFF delay time is the time from a valid input signal to recognition by the module.
If an output exceeds 1.5 A for greater than 7 ms, a fault is generated.
Input and Output Ratings
Supply Voltage
Type of Inputs
Connection Type
Input per Connection
Rated Operating Voltage
On-State Input Voltage (pin 4)
Off-State Input Voltage
On-State Input Current (pin 4)
Off-State Input Current
Maximum Sensor Leakage Current
Maximum Number of Input Devices
Maximum Sensor Sourcing Current (pin 1)
Sensor Operating Voltage Range
Input Bounce Filter
(Software Configurable)
Filtering
DeviceLogix I/O Response
Supply Voltage (Switched Power)
Type of Outputs
Load Types
Utilization Category (IEC)
Output State
Connection Type
Output per Connection
Overcurrent Protection
Rated Insulation Voltage (U
)
i
Rated Operating Voltage (U
)
e
Maximum Blocking Voltage
Nominal Operating Current (I
)
e
Maximum Thermal Current (I
)
the
Maximum Off-state Leakage Current
Maximum Number of Outputs
Surge Suppression
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Specifications
Unswitched power A3/A2
24V DC current sinking
Single keyed M12, quick disconnect
1/each
24V DC
10...26.4V DC, nominal 24V DC
5V DC
1...3.7 mA, 2.6 mA @ 24V DC
<1.5 mA
<2.5 mA
6
50 mA per point (max 300 mA total for sourcing one device)
19.2...26V DC
Off-On or On-Off: 0.5 ms + 64 ms
100 μs
2 ms (500 Hz)
A1/A2
DC sourcing
Resistive or light inductive
DC-1, DC-13
Normally Open (N.O.)
Single keyed M12, quick disconnect
1/each
1.5 A (the sum of all outputs cannot exceed this value)
UL: 1500V AC, IEC: 2000V AC
19.2...26.4V DC
35V DC
500 mA per point
500 mA per point
1 μA
6
Integrated diode to protect against switching loads
Chapter 6
167