Chapter 6
Specifications
Input
Output
Input ON-to-OFF delay time is the time from a valid input signal to recognition by the module.
If an output exceeds 1.5 A for greater than 7 ms, a fault is generated
174
Input and Output Ratings
Supply Voltage
Type of Inputs
Connection Type
Input per Connection
Rated Operating Voltage
On-State Input Voltage (pin 4)
Off-State Input Voltage
On-State Input Current (pin 4)
Off-State Input Current
Maximum Sensor Leakage Current
Maximum Number of Input Devices
Maximum Sensor Sourcing Current (pin 1)
Sensor Operating Voltage Range
Input Bounce Filter
(Software Configurable)
Filtering
DeviceLogix I/O Response
Supply Voltage (Switched Power)
Type of Outputs
Load Types
Utilization Category (IEC)
Output State
Connection Type
Output per Connection
Overcurrent Protection
Rated Insulation Voltage (U
Rated Operating Voltage (U
Maximum Blocking Voltage
Nominal Operating Current (I
Maximum Thermal Current (I
Maximum Off-state Leakage Current
Maximum Number of Outputs
Surge Suppression
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Unswitched power A3/A2
24V DC current sinking
Single keyed M12, quick disconnect
10...26.4V DC, nominal 24V DC
1...3.7 mA, nominal 2.6 mA @ 24V DC
50mA per point (max 300mA total for sourcing one device)
Off-On or On-Off: 0.5 ms + 64 ms
Resistive or light inductive
Normally Open (N.O.)
Single keyed M12, quick disconnect
1.5 A (the sum of all outputs cannot exceed this value)
)
UL: 1500V AC, IEC: 2000V AC
i
)
e
)
e
)
the
Integrated diode to protect against switching loads
1/each
24V DC
5V DC
<1.5 mA
<2.5 mA
6
19.2...26V DC
100 μs
2 ms (500 Hz)
A1/A2
DC sourcing
DC-1, DC-13
1/each
19.2...26.4V DC
35V DC
500 mA per point
500 mA per point
1 μA
6