Allen-Bradley ArmorStart 290E User Manual page 137

Lt distributed motor controller
Table of Contents

Advertisement

Figure 53 - S Curve
Example:
Accel Time = 10 Seconds
S Curve Setting = 50%
S Curve Time = 10 x 0.5 = 5 Seconds
Total Time = 10 + 5 = 15 Seconds
JogFrequency
Sets the output frequency when the jog
command is issued.
JogAccelDecel
Sets the acceleration and deceleration
time when a jog command is issued.
Rockwell Automation Publication 290E-UM001B-EN-P - June 2012
Bulletin 290E/291E/294E Programmable Parameters
50% S Curve
Target
Target 2
1/2 S Curve Time
Accel Time
2.5 Seconds
10 Seconds
Total Time to Accelerate = Accel Time + S Curve Time
Parameter Number
Related Parameters
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Parameter Number
Related Parameters
Access Rule
Data Type
Group
Units
Minimum Value
Maximum Value
Default Value
Chapter 4
1/2 S Curve Time
2.5 Seconds
39
35, 40
GET/SET
UINT
Drive Advanced Setup
x.x Hz
0.0
400.0
10.0
40
39
GET/SET
UINT
Drive Advanced Setup
x.x secs
0.1
600.0
10.0
137