7.3 Connecting The External Proximity Reader (PCX-EXT-BK)

The External Proximity Reader can be used as either an arm,
disarm, entry control or an access control device.
NOTE: See the reader installation manual for the LED and
button explanations.
NOTE: The total number of readers that can be installed on
the
is 5. The readers are installed on the same
PCX 46 APP
bus as the keypads.
7.3.1 Technical Specification
PCX-EXT-BK / W (External Tag Reader)
Supply voltage:
Current consumption:
Input status when reader is Arm/Disarm or Sub-Area Control:
Input:
Input EOL fixed resistor
value:
Input status when reader is used as Access or Door Entry Control:
Input 1:
Input Function:
Input 2:
Note: Access control falls outside the scope of EN 50131
Output 1:
Output 2:
Output 1/2 Normal state:
Output 1/2 Active state:
Colour and Casing:
Potted
Temperatures:
Dimensions (H x W x D):
IP65 Rated. If the control panel fails to arm, this is indicated by a broken tone on the external
proximity reader and the red LED will not illuminate. If this occurs, please check the
information at the nearest keypad.
7.3.2 Addressing the External Tag Reader (From the Reader)
PCX 46 App Installation Reference
9-15VDC
Max 22mA
Programmable. DEOL
Alarm=4K7 / Tamper=2K2
Normal: 1k4 to 2k9
Burglary Alarm:4k2 to 7k8
Tamper: <1k4 or >22k
Programmable
Door monitor feature. Door opening time limit is programmable from the
Engineer Menu
Not programmable
Not programmable. Activates the Door Lock Relay
Not programmable. Door monitor alarm activation (forced or open for longer
than programmed time).
Floating
0V
3mm ABS (Black: PCX-EXT-BK, White: PCX-EXT-W)
Type B
Storage: -10°C to 50°C
Certified: -25°C to 60°C
Nominal: -25°C to 60°C
85 x 85 x 21mm