8.4 Connecting to the Upload/Download Software

The
control panel can be programmed by the LCD menu or the UDL InSite Software provided
PCX 46 APP
free of charge. It can be downloaded from http://www.pyronix.com/pyronix-downloads.php. The
connection between control panel and UDL software can be done in the following ways:
8.4.1 Serial Connection (RS232)
1. Enter the Engineer menu (code 9999)
2. Scroll the menu (x button) until the "Options Up/Downloading"
3. Choose RS-232 in the "Download by" option – Press t
4. Now on the 'UDL Password' screen – DO NOT USE – leave blank and Press t
5. Now on the 'Site Name' screen – this is optional – if you enter a site name, make sure that you
take a note of it for use later in the Insite software – or leave blank – then press t
6. Now on the 'UDL Priority' screen – we recommend setting this to High [0] (which prevents
App events / notifications from disconnecting the UDL connection).
HomeContol+
8.4.2 On InSite UDL software from a PC
1. To setup the COM port associated to "modem" open the software, click on "Configuration", -
choose "Modem Settings" and select "RS-232" option
2. Make sure that the serial COM used by UDL is the set the same in the PC
(Control Panel -> Device Manager -> Ports)
3. Make sure that the UDL Graphic user interface has the RS-232 icon green colored and glowing
4. Click on "Force Dial Customer"
5. Set "Dial Mode" field to "RS-232"
6. Enter the Engineer code in the "Engineer Code" field
7. Click on "dial"
8. If connection is successful, the RS-232 icon will become blue
PCX 46 App Installation Reference