Read and understand the following notes while planning and performing the installation:
As a result of the connected loads high leakage current is possible. Connection to earth ground is required for
safety and proper product operation. Do not check IBC operation by any action that includes removal of the
earth (ground) connection with loads attached.
Refer to national and local electrical codes for acceptable external wiring practices.
Material and labor for external wiring requirements are to be provided by the customer.
For external wiring, use 75°C copper wire. Wire sizes listed in
only. If wire is run in an ambient temperature greater than 40°C, higher temperature wire and/or larger size
wire may be necessary. Wire sizes are based on using the specified breakers.
Recommended wire sizes are based on NFPA National Electrical Code® (NEC®)70 Table 310.15(B)(16) 75°
C ampacity with 40°C ambient correction factors.
The battery wiring used between the battery and the UPS for standalone installations should be a
maximum of 20 meters (65 feet) with a voltage drop of less than 1% of nominal DC voltage at rated
battery current.
Refer to NEC Article 250 and local codes for proper grounding practices.
Battery voltage is computed at 2 volts per cell as defined by Article 480 of the NEC. Rated battery current
is computed at 2 volts per cell.
The battery cabinet frame is not referenced to the DC circuit.
Each battery cabinet has its own overcurrent protection device.
Internal battery strings are to be connected by an authorized Eaton Customer Service Engineer.
Refer to the appropriate Eaton 93PM UPS Installation and Operation manual listed in paragraph
1.7 For More Information
The term line-up-and-match refers to accessory cabinets that are physically located adjacent to the UPS.
The term standalone refers to accessory cabinets that are located separate from the UPS.
For line-up-and-match external power wiring requirements, including the minimum AWG size of external wiring,
see
Table
3. For standalone external power wiring requirements, including the minimum AWG size of external
wiring, see
Table
4. Wire sizes listed are for copper wiring only.
Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06
WARNING
for UPS cabinet conduit and terminal specifications and locations.