Product Specifications
7 7 . . 2 2 . . 2 2 E E n n v v i i r r o o n n m m e e n n t t a a l l a a n n d d S S a a f f e e t t y y S S p p e e c c i i f f i i c c a a t t i i o o n n s s
Operating Temperature
Transit Temperature
Storage Temperature
Operating Altitude
Transit Altitude
Ventilation
Relative Humidity (operating and
storage)
Acoustical Noise
Safety Conformance
Agency Markings
EMC (Class A)
56
Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06
The battery cabinet is rated for operation in up to a 40°C (104°F) ambient
temperature.
NOTE Emergency lighting and power equipment battery cabinets (UL924) are rated
for operation in a 20°–30°C (68°–86°F) temperature environment.
The batteries are rated for a 25°C (77°F) ambient temperature to extend their useful
life.
-25°C to 60°C (-13°F to 140°F)
Recommended NPX-80RFR Battery Transit: -20°C to 50°C (-4°F to 122°F)
-25°C to 55°C (-13°F to 131°F)
Recommended NPX-80RFR Battery Storage: -20°C to 50°C (-4°F to 122°F))
Maximum 1500m (5000 ft) at 40°C without derating
15000m (49213 ft)
Convection
95%, noncondensing
Not applicable
UL1778 4
th
edition
cULus
FCC Part 15 Class A and 62040-2 c3