Figure 16. DC Power Terminal Detail – Eaton 93PM Integrated Battery Cabinet-Small
IBC DC (+) Output
To UPS Positive
Terminals (+)
IBC DC (-) Output
To UPS Negative
Terminals (-)
4 4 . . 3 3 . . 2 2 S S t t a a n n d d a a l l o o n n e e P P o o w w e e r r W W i i r r i i n n g g
NOTE 1
Each battery cabinet will be directly connected to the UPS and not daisy-chained
between cabinets.
NOTE 2
Standalone IBC installations with three or four IBCs require a customer supplied external
tie point and circuit breaker or disconnect between the IBCs and the UPS.
NOTE 3
Up to four IBCs can be installed in a standalone configuration.
NOTE 4
In multiple IBC installations, individual conduit will be run between each battery cabinet
and the UPS or disconnect. DO NOT run battery wiring from subsequent IBCs through
the bottom of the adjacent IBCs.
NOTE 5
Remove the IBC conduit landing plates to drill or punch conduit holes, or remove
knockouts in the conduit plate.
Use this procedure to wire standalone 93PM Integrated Battery Cabinets to the 93PM UPS cabinet.
To install wiring to connections:
TB2