Installation Plan and Unpacking
NOTE
The batteries are rated for a 25°C (77°F) ambient temperature to extend their useful life.
Maximum Relative Humidity: 95%, noncondensing
It is recommended for optimal battery life and discharge performance to keep the ambient air temperature the
battery is used in at 25°C (77°F). Operating temperatures above the recommended range will result in
decreased battery life and performance, and will reduce or void the battery warranty. Refer to Eaton's Terms
and Conditions of Sale with Battery Replacement Coverage and the Battery Replacement Price Book for more
information. These documents can be found at www.eaton.com/powerquality or contact your service
representative for information on how to obtain copies.
The shelf life for the batteries installed in the IBC is 12 months from the date code on the battery. The recharge
date is also stated on a label inside the IBC.
Failure to recharge the batteries before the expiration of the shelf life will result in reduced discharge time,
shorter float service life, and will void the warranty.
The IBC operating environment must meet the weight requirements shown in
requirements shown in
subject to change.
Table 1. IBC-S Cabinet Weights
Eaton 93PM IBC-S with NPX-80RFR
The IBC uses natural convection cooling to regulate internal component temperature. Air inlets are in the front
of the cabinet and outlets are on the back or top of the cabinet. Allow clearance in front of, and on back or top
of the cabinet for proper air circulation. The clearances required around the IBC cabinet are shown in
12
Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06
Emergency lighting and power equipment battery cabinets (UL924) are rated for
operation in a 20°–30°C (68°–86°F) temperature environment.
Figure 3
through
# of Battery
Strings
Model
Batteries
No Batteries
CAUTION
CAUTION
Figure
6. Dimensions are in millimeters (inches). Specifications are
Shipping
2
762 (1680)
3
1012 (2230)
300 (662)
Table 1
and the size
Weight kg (lb)
Point Loading
Installed
740 (1632)
4 at 185 (408)
990 (2182)
4 at 248 (546)
269 (592)
4 at 69 (148)
Table
2.