Installing Ibc Interface Wiring - Eaton 93pm Installation Manual

Table of Contents

Advertisement

15. Route the battery cabinet ground wiring from the UPS through the bottom of the IBC to the IBC ground
terminal block. See
16. Connect the positive and negative power wiring to the IBC DC (+) and DC (-) output terminals. Connect the
ground wiring to the ground terminal on the IBC. See
For a detailed view of the IBC terminal block, see
17. Connect the positive, negative, and ground DC power wiring from the IBC or disconnect to the UPS
cabinet battery and ground terminals. Refer to the applicable Eaton 93PM UPS Installation and Operation
manual listed in paragraph
NOTE
18. If installing more than one IBC, repeat Steps
paragraph
4.4 Installing IBC Interface
NOTE
Figure 17. IBC-S Top and Bottom Entry Conduit and Wire Entry Locations
Top Entry Conduit
Landing for DC Output
(Remove panel to drill
or punch conduit holes.)
4 4 . . 4 4
I I n n s s t t a a l l l l i i n n g g I I B B C C I I n n t t e e r r f f a a c c e e W W i i r r i i n n g g
IBCs can be installed in a line-up-and-match configuration with the interface wiring routed through the IBCs and
UPS cabinet or in a standalone configuration with the interface wiring routed between the IBCs and the UPS
cabinet using conduit.
Figure 14
for terminal location.
1.7 For More
If installing more than one IBC, individual conduit will be run between each battery
cabinet and the UPS or disconnect. DO NOT run battery wiring from subsequent IBCs
through the bottom of the adjacent IBCs.
4.4 Installing IBC Interface
Wiring.
Internal battery strings are to be connected by an authorized Eaton Customer Service
Engineer at system startup.
Top View
Eaton 93PM Integrated Battery Cabinet-Small (IBC-S) Installation Manual 164000305—Rev 06
Table 5
for termination requirements.
Figure
16.
Information, for UPS cabinet termination requirements.
Step 12
through
Step 17
Wiring; otherwise, proceed to paragraph
Bottom View
Installation
for each IBC, and then proceed to
Bottom Entry Conduit
Landing for DC Output
(Remove panel to drill
or punch conduit holes.)
35

Advertisement

Table of Contents
loading