Mitsubishi Electric Melsec iQ-R Series User Manual page 124

Hart-enabled analog-digital converter module
Hide thumbs Also See for Melsec iQ-R Series:
Table of Contents

Advertisement

CH1 Range setting
This area is for setting an input range.
Setting value
0H
1H
AH
• If a value other than the above is set, a range setting range error (error code: 190H) occurs.
• The input range cannot be switched for the channel where A/D conversion disable is set. To switch the input range, set
'CH1 A/D conversion enable/disable setting' (Un\G500) to A/D conversion enable (0) and turn on and off 'Operating
condition setting request' (Y9).
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Range setting
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 4 to 20mA (0H) for all channels.
APPX
122
Appendix 3 Buffer Memory Areas
Setting details
4 to 20mA
0 to 20mA
4 to 20mA (extended mode)
CH1
CH2
CH3
598
798
998
CH4
CH5
CH6
1198
1398
1598
CH7
CH8
1798
1998

Advertisement

Table of Contents
loading

Table of Contents