Detection method
Select a detection method from the following table.
Detection method
Detection condition
0: Disable
Input signal errors are not detected.
1: Upper and lower limit
An input signal error is detected when the
detection
analog input value is equal to or greater
than the input signal error detection upper
limit value, or when the analog input value
is equal to or smaller than the input signal
error detection lower limit value.
2: Lower limit detection
An input signal error is detected when the
analog input value is equal to or smaller
than the input signal error detection lower
limit value.
3: Upper limit detection
An input signal error is detected when the
analog input value is equal to or greater
than the input signal error detection upper
limit value.
4: Simple disconnection
Simple disconnection detection is performed. For details, refer to the following.
Page 42 Simple disconnection detection
detection
I: Analog input value
t: Time
In
: Input signal error detection upper limit value
H
In
: Input signal error detection lower limit value
L
I
Error detection
In
H
In
L
Error detection
I
No error detection
In
H
In
L
Error detection
I
Error detection
In
H
In
L
No error detection