Maximum value/minimum value reset completed flag
'Maximum value/minimum value reset completed flag' (XD) turns on after the maximum and minimum values stored in 'CH1
Maximum value' (Un\G404) and 'CH1 Minimum value' (Un\G406) are reset by turning on and off 'Maximum value/minimum
value reset request' (YD).
'CH1 Maximum value' (Un\G404)
'CH1 Minimum value' (Un\G406)
'Maximum value/minimum value reset
request' (YD)
'Maximum value/minimum value reset
completed flag' (XD)
Performed by the A/D converter module
Performed by a program
■Device number
The following shows the device number of this input signal.
Signal name
Maximum value/minimum value reset completed flag
A/D conversion completed flag
'A/D conversion completed flag' (XE) turns on when the first A/D conversion of all the channels where the A/D conversion is
enabled is completed. To read digital output values, use this signal or 'A/D conversion completed flag' (Un\G42) as an
interlock.
■Device number
The following shows the device number of this input signal.
Signal name
A/D conversion completed flag
Error flag
'Error flag' (XF) turns on when an error occurs.
Turn on and off 'Error clear request' (YF) to clear 'Latest error code' (Un\G0) and 'Latest alarm code' (Un\G2).
'Latest error code' (Un\G0)
'Error flag' (XF)
'Error clear request' (YF)
Performed by the A/D converter module
Performed by a program
■Device number
The following shows the device number of this input signal.
Signal name
Error flag
APPX
92
Appendix 2 I/O Signals
ON
ON
CH1
XD
CH1
XE
0
Error code
ON
CH1
XF
OFF
OFF
CH2
CH3
CH4
CH2
CH3
CH4
0
OFF
ON
OFF
CH2
CH3
CH4
CH5
CH6
CH7
CH5
CH6
CH7
CH5
CH6
CH7
CH8
CH8
CH8