CH1 Warning output setting (Rate alarm)
Set whether to enable or disable the warning output of a rate alarm.
For details on the warning output function (rate alarm), refer to the following.
Page 35 Rate alarm
Setting value
0
1
If a value other than the above is set, a warning output setting (Rate alarm) range error (error code: 1B8H) occurs.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Warning output setting (Rate alarm)
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is Disable (1) for all channels.
CH1 Process alarm upper upper limit value
Set an upper upper limit value of the warning output function (process alarm).
For details on the warning output function (process alarm), refer to the following.
Page 32 Process alarm
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
CH Process alarm upper upper limit value
■Setting range
The setting range is from -32768 to 32767.
■Enabling the setting
Turn on and off 'Operating condition setting request' (Y9).
■Default value
The default value is 0 for all channels.
APPX
116
Appendix 3 Buffer Memory Areas
Setting details
Enable
Disable
CH1
CH2
CH3
513
713
913
CH1
CH2
CH3
514
714
914
CH4
CH5
CH6
1113
1313
1513
CH4
CH5
CH6
1114
1314
1514
CH7
CH8
1713
1913
CH7
CH8
1714
1914