Warning output flag (Rate alarm lower limit)
The lower limit warning of the rate alarm can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Alarm ON
(2) b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Warning output flag (Rate alarm lower limit)
■Warning output flag status
• When a value is out of the range specified in 'CH1 Rate alarm lower limit value' (Un\G526), Alarm ON (1) is stored in the
corresponding bit of 'Warning output flag (Rate alarm lower limit)' (Un\G39).
• When a warning is detected in any channel where the A/D conversion and the warning output setting (rate alarm) are
enabled, 'Warning output signal' (X8) also turns on.
■Clearing Warning output flag
• When the change rate of the digital output value falls within the set range, the flag is automatically cleared.
• When 'Operating condition setting request' (Y9) is turned on and off, the flag is cleared.
Input signal error detection flag
The status of an input signal can be checked for each channel.
b15 b14 b13 b12 b11 b10 b9
0
0
0
0
0
0
0
(2)
(1) 0: Normal, 1: Input signal error
(2) b8 to b15 are fixed to 0.
■Buffer memory address
The following shows the buffer memory address of this area.
Buffer memory name
Input signal error detection flag
■Input signal error detection flag status
• When an analog input value out of the range set with 'CH1 Input signal error detection setting value' (Un\G529) is detected,
Input signal error (1) is stored in the corresponding bit of 'Input signal error detection flag' (Un\G40).
• When an error is detected in any channel where the A/D conversion and the input signal error detection are enabled, 'Input
signal error detection signal' (XC) turns on.
■Clearing Input signal error detection flag
When 'Error clear request' (YF) is turned on and off after the cause of the input signal error is eliminated and the analog input
value falls within the set range, 'Input signal error detection flag' (Un\G40) turns off. When 'Input signal error detection flag'
(Un\G40) turns off, the following operations are performed.
• The ALM LED turns off.
• 'Input signal error detection signal' (XC) turns off.
• 'Latest alarm code' (Un\G2) is cleared.
Turning on and off 'Operating condition setting request '(Y9) also clears 'Input signal error detection flag' (Un\G40). However,
the A/D conversion is reset and the processing is started from the beginning.
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
39
b8
b7
b6
b5
b4
b3
b2
0
CH8
CH7
CH6
CH5
CH4
CH3
CH2
(1)
CH1
40
b1
b0
CH1
CH2
CH3
CH4
b1
b0
CH1
CH2
CH3
CH4
CH5
CH6
CH7
CH8
CH5
CH6
CH7
CH8
APPX
Appendix 3 Buffer Memory Areas
A
107

Advertisement

Table of Contents
loading

Table of Contents